Over-voltage of Capacitor Module (ECM)
Fanuc · Macro B CNC Programming
What does 7 mean?
An over-voltage condition has occurred in the Energy Charge Module's Capacitor Modules. This implies the capacitor bank is being charged beyond its rated voltage, potentially due to a fault in the charging control circuit, an issue with the Resistor Module, or an external over-voltage condition.
Common Causes
- Excessive voltage detected on the capacitor module (ECM) exceeding P1-75 limit.
- Faulty power supply unit (ECM) supplying unstable voltage.
- Incorrect input voltage configuration for the ECM.
- Capacitor degradation leading to overcharge during operation.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Immediately stop the machine using the emergency stop button and open the external Main Circuit Contactor (MCC) of the Power supply.
- 2
Measure the voltage across the Capacitor Modules (A06B-6158-H020) to confirm the over-voltage condition.
- 3
Inspect the charging control circuit of the ECM (Control Module A06B-6158-H010) for proper regulation of the charging voltage.
- 4
Verify the functionality of the Resistor Module (A06B-6158-H030), ensuring it can effectively discharge the Capacitor Modules at Emergency Stop or Alarm (page 578).
- 5
Check the main power supply and any connected regenerative units for conditions that could lead to excessive voltage accumulation in the Capacitor Modules.