Fanuc · Macro B CNC Programming
The 24V control power supply voltage to the Energy Charge Module (ECM) or Servo amplifier is low. This critical condition prevents proper operation of the ECM and associated components, indicating a problem with the external 24V power source or its connections.
Click steps to track your progress.
Immediately stop the machine using the emergency stop button and open the external Main Circuit Contactor (MCC) of the Power supply.
Measure the 24V DC input voltage at the control power supply terminals to the ECM and servo amplifier; ensure it is stable and within the acceptable range (e.g., 24V ±10%).
Check the external power supply unit providing the 24V control power for proper output voltage and sufficient capacity.
Inspect the wiring and connections of the 24V control power supply for any loose connections, breaks, or excessive voltage drop due to long or undersized cables.
Verify the total load on the 24V control power supply. Excessive load from other devices could cause the voltage to drop below acceptable levels.