This alarm indicates an undervoltage condition in the control power supply of the Inverter (Servo Amplifier). This can be caused by low three-phase input voltage, insufficient 24V power supply from the Power Supply, or issues with the CXA2A/B connector and cable.
Click steps to track your progress.
Check the three-phase input voltage of the amplifier — ensure it is not lower than 85% of the rated input voltage.
Check the 24V power supply voltage output from the Power Supply — ensure it is not lower than 22.8V.
Check the connector and cable (CXA2A/B) for proper connection and integrity.
Replace the Servo Amplifier if voltage and cable checks are satisfactory.