This code indicates a complete absence of an AC grid connection, preventing the inverter from feeding energy. The inverter will automatically attempt to connect again once an AC grid is detected.
Click steps to track your progress.
Check the AC voltage on the inverter connection sockets; it must be 220/230 V (+10% / -5%) or 380/400 V (+10% / -5%).
Verify that all AC circuit breakers leading to the inverter are closed and functional.
Inspect all AC cable connections for integrity and secure termination.