Fronius · Primo GEN24 Operating Instructions
This code indicates that the DC input voltage from the PV string connected to Maximum Power Point Tracker 2 (MPPT 2) is too high. This triggers a short-term interruption in energy feeding, and the inverter will attempt to resume its startup routine.
Click steps to track your progress.
If the status code is displayed continuously, notify a Fronius-trained service engineer.
Verify the open-circuit voltage (Voc) of the PV string connected to MPPT2 and ensure it is within the inverter's specified limits.
Reconfigure or modify the PV string connected to MPPT2 if its voltage exceeds the inverter's rating.