Fronius · Symo Advanced
This status code indicates that the AC grid impedance is too high, preventing the Fronius Primo GEN24 208-240 inverter from operating correctly. This can be caused by long or undersized AC cables, or a generally weak utility grid connection.
Click steps to track your progress.
Inspect the AC grid connection point for loose terminals or poor contact.
Verify the AC cabling to the inverter terminals (wire gauge and length) and ensure it meets installation guidelines to minimize impedance.
Observe the stability of the AC grid by monitoring voltage and current under load.
De-energize the inverter (switch off AC and DC disconnects), wait for 5 minutes, then re-energize to reset. If the message persists, the inverter may require service.