Fronius · Symo Advanced
The Rapid Shutdown (RSD) function was automatically activated due to the inverter detecting a loss of the grid connection. This event, typically an interruption by an AC breaker, causes the inverter to discharge the PV module terminals to less than 30 VDC and less than 15 VAC within 30 seconds.
Click steps to track your progress.
Verify the status of the public AC grid connection to the inverter.
Inspect the AC breaker(s) supplying the inverter to ensure they are in the closed position and have not tripped.
Confirm that there are no external conditions causing an AC grid interruption.