%.1s motor enc. line count too high
Heidenhain · NC Control
What does 2189 F060 mean?
The configured motor encoder line count for the displayed axis is too large. This indicates a mismatch between the encoder's actual resolution and the value set in the NC control's parameters.
Common Causes
- Motor encoder line count too large for the displayed axis.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the configured motor encoder line count parameter for the specified axis in the NC control against the actual motor encoder's nameplate data or datasheet.
- 2
Ensure the encoder type and resolution are compatible with the NC control's specifications for that axis.
- 3
Check the motor encoder cabling for any signs of interference, damage, or improper shielding that could lead to erroneous readings.
- 4
If the parameter is correct, consider if an incorrect encoder model with a higher line count has been installed or if there's a fault in the control's encoder signal processing hardware.