7952 A820

CC speed greater than SRG %.2s

Heidenhain · NC Control

What does 7952 A820 mean?

The maximum permissible velocity in the SRG (Safe Reduced Speed) operating mode was exceeded for the specified axis. This indicates a safety violation where the axis moved too fast for the active safe reduced speed conditions.

Common Causes

  • Maximum permissible velocity in the SRG operating mode was exceeded.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Reduce the programmed feed rate and shaft speed before opening the safety doors or engaging SRG operating mode.

  2. 2

    Verify the position of the key-operated switch to ensure the correct operating mode (e.g., BA2, BA3, BA4, Special operation) is selected and active.

  3. 3

    Check the parameter values: MP540.x/MP541 (Operating mode BA3/BA4), MP552.x/MP551 (Special operation), and MP590.x/MP591 (Operating mode BA2) to confirm their settings match the machine's safety configuration.

  4. 4

    Inspect the safety door interlocks and the axis speed monitoring system for proper function and calibration.

Browse all codes in this manual (58)