Heidenhain · TNC CNC Controllers
This error signifies a short circuit on the +24 V line of the T.BRK.B signal, detected during a braking control test. Specifically, a +24 V signal level is present at the -T.BRK.B input of the SPL module when 0 V is expected, indicating an issue with the brake control circuit.
Click steps to track your progress.
Inspect the external wiring of the brakes and the T.BRK signal for any damage, short circuits, or loose connections.
Measure the voltage at the -T.BRK.B input of the SPL module when 0 V is commanded by the control; it should read 0 V.
Check the functionality of the relay responsible for brake control. Verify its coil and contact states.
Perform continuity tests on the T.BRK.B signal line to ensure no unintentional connection to +24 V.