Heidenhain · TNC CNC Controllers
This error signifies a problem during the dynamic test of the second emergency-stop loop in the Heidenhain TNC CNC Controller. During this safety test, a 0V signal is expected at input NE2 within 1.5 minutes. If a 24V signal remains present, it indicates a failure in the emergency-stop circuit, compromising the machine's safety function.
Click steps to track your progress.
Verify the wiring of input NE2 and the entire second emergency-stop loop for continuity, proper terminations, and any signs of damage or short circuits.
Inspect all emergency-stop buttons connected to the second loop for mechanical damage, correct operation, and ensure their contacts transition correctly (normally closed) when activated.
Measure the voltage at input NE2 during the dynamic test sequence; confirm that it transitions to 0V as expected within the 1.5-minute timeout.
If wiring and emergency-stop buttons are confirmed functional, consult a Heidenhain service agency for further diagnostics on potential hardware defects in the safety monitoring module.