Huawei · SUN2000-(3KTL-10KTL)-M1 Solar Inverter
The number of PV modules connected in series to the PV string is insufficient, resulting in a lower end voltage compared to other parallel strings. This can lead to inefficient operation or potential current backfeed issues.
Click steps to track your progress.
Check whether the number of PV modules connected in series to this PV string is less than that of the other PV strings connected in parallel. If so, wait until the PV string current decreases to below 0.5 A, turn off the DC switch, and adjust the number of PV modules in the PV string.
Check whether the PV string is shaded.
Check whether the open-circuit voltage of the PV string is abnormal.