Huawei · SUN2000 8-28KTL Solar Inverter
A major fault indicating that the connected grid voltage is outside the allowed range, or there is a large difference in voltage among the three phases, or a power outage/AC line disconnection. This prevents grid synchronization and power export, leading to inverter shutdown.
Click steps to track your progress.
For Reason ID = 1 to 6, observe if the SUN2000 automatically reverts to normal operating status if the alarm occurred accidentally.
For Reason ID = 1 to 6, if the alarm occurs repeatedly, check if the grid voltage is within the allowed range. If so, change the grid overvoltage and undervoltage protection points after obtaining approval from the local power operator (refer to 7.2.9 Setting Protection Parameters).
For Reason ID = 1 to 6, if the alarm persists for a long time, check that the AC circuit breaker and output cables of the SUN2000 are properly connected.
For Reason ID = 13 to 18, or 26, check if the grid-tied point voltage is too high. If it is higher than the allowed range, change the overvoltage and undervoltage protection points after obtaining approval from the local power operator (refer to 7.2.9 Setting Protection Parameters). Also, check whether the grid voltage peak is too high.
For Reason ID = 27 or 28, observe if the SUN2000 automatically reverts to normal operating status.
For Reason ID = 29, check whether the AC voltage is normal and whether the AC line or circuit breaker is disconnected.