305

Frequency Abnormal

Huawei · SUN2000 8-28KTL Solar Inverter

What does 305 mean?

A major fault indicating that the actual frequency of the connected power grid is outside the required range for the local grid. This can prevent the SUN2000 from synchronizing and feeding power, leading to shutdown.

Common Causes

  • The actual frequency of the grid is higher than or lower than the required value for the local grid.
  • An accidental grid abnormality.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Observe if the SUN2000 automatically reverts to normal operating status if the alarm occurred accidentally due to a temporary grid abnormality.

  2. 2

    If the alarm occurs repeatedly, check if the grid frequency is within the allowed range.

  3. 3

    If the grid frequency is within the allowed range but alarms persist, change the grid overfrequency and underfrequency protection points after obtaining approval from the local power operator (refer to 7.2.9 Setting Protection Parameters).