313

Low Array Insulation Resistance

Huawei · SUN2000 8-28KTL Solar Inverter

What does 313 mean?

A major fault where the insulation resistance of the PV strings against ground is low, potentially due to a short circuit between strings and ground or installation in a permanently moist environment. This poses a safety risk and can lead to inverter shutdown.

Common Causes

  • A short circuit between PV strings and the ground.
  • The PV strings are installed in a permanently moist environment.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the insulation resistance against the ground of the PV strings.

  2. 2

    If a short circuit is detected, rectify the fault.

  3. 3

    If the insulation resistance against the ground is less than the default value in a rainy environment, set the ISO value (refer to 7.2.9 Setting Protection Parameters).