Huawei · SUN2000 Solar Inverter
The N (Neutral) cable or ground cable is not properly connected, or if a PV array is grounded, the inverter output is not connected to an isolation transformer. This indicates a potential safety hazard due to incorrect grounding.
Click steps to track your progress.
Power off the inverter.
Check whether the PE cable of the SUN2000 is connected properly.
If the inverter is connected to the TN power grid, check whether the N cable is properly connected and whether the voltage of the N cable to ground is normal.
Check whether the output is connected to an isolation transformer. If yes, set 'Grounding inspection' to 'Disable' through the mobile phone app, SmartLogger, or NMS.