2085

Built-in PID operation abnormal

Huawei · SUN2000 Solar Inverter

What does 2085 mean?

This Minor alarm indicates an issue with the built-in Potential Induced Degradation (PID) operation. It can be caused by low output resistance of PV arrays to ground or low system insulation resistance, affecting the compensation function.

Common Causes

  • The output resistance of PV arrays to ground is low.
  • The system insulation resistance is low.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Turn off the AC output switch and DC input switch.

  2. 2

    Wait for the specified time (as per device safety warning label), then turn on the DC input switch and AC output switch.

  3. 3

    Check the impedance between the PV array output and the ground. Rectify any short circuits or insufficient insulation.