E252

Bleeder Overtemperature Warning

Indramat · ECODRIVE Controller

What does E252 mean?

The internal or external braking resistor (bleeder) has reached a high operating temperature, nearing its maximum permissible limit. This warning indicates that continuous operation under these conditions may lead to an F220 shutdown of the ECODRIVE DKC01.1/DKC11.1 drive.

Common Causes

  • Excessive regenerative energy due to frequent or rapid decelerations, or heavy overhauling loads.
  • Improperly sized or faulty external braking resistor.
  • Inefficient cooling or poor ventilation for the braking resistor.
  • Overloading of the drive's internal bleeder circuit.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the duty cycle and deceleration rates of the application; consider extending deceleration times or reducing frequency.

  2. 2

    Inspect the external braking resistor for signs of overheating, proper connection, and verify its ohmic value.

  3. 3

    Ensure adequate airflow and ventilation around the braking resistor and within the control cabinet.

  4. 4

    Evaluate if the braking resistor is appropriately sized for the regenerative energy profile of the application.

  5. 5

    Monitor the DC bus voltage during braking events and the temperature of the bleeder if possible.

Browse all codes in this manual (24)
Verified technical data. Last updated: April 2026