Indramat · ECODRIVE Controller
The internal or external braking resistor (bleeder) has reached a high operating temperature, nearing its maximum permissible limit. This warning indicates that continuous operation under these conditions may lead to an F220 shutdown of the ECODRIVE DKC01.1/DKC11.1 drive.
Click steps to track your progress.
Verify the duty cycle and deceleration rates of the application; consider extending deceleration times or reducing frequency.
Inspect the external braking resistor for signs of overheating, proper connection, and verify its ohmic value.
Ensure adequate airflow and ventilation around the braking resistor and within the control cabinet.
Evaluate if the braking resistor is appropriately sized for the regenerative energy profile of the application.
Monitor the DC bus voltage during braking events and the temperature of the bleeder if possible.