Indramat · ECODRIVE Controller
The drive has received a command value that resulted in the axis reaching a position outside the defined negative travel range. The axis is stopped by setting the velocity command value to zero. This is treated as a warning when Bit 2 of S-0-0090 (Command Value Transmit Time - TMTSG) is set to "Exceeding the travel limit is considered as a warning", allowing automatic recovery if command values lead back to the valid range.
Click steps to track your progress.
Specify command values that lead the axis back into the valid negative travel range.
Verify the physical installation and functionality of the negative travel limit switch.
Check the commanded position or motion profile from the control system to ensure it respects the defined travel limits.
Review the parameter S-0-0090 (Command Value Transmit Time - TMTSG), specifically Bit 2, to understand the drive's reaction to exceeding travel limits.