Indramat · ECODRIVE Controller
The drive was unable to process the given command value, resulting in a deviation from the commanded position/velocity that exceeded an allowable limit. The drive reacted by shutting down according to the set error reaction to prevent mechanical damage or uncontrolled movement.
Click steps to track your progress.
Check the Bipolar Torque Limit, parameter S-0-0092, and ensure it is set to the maximum allowable value for the application and motor.
Inspect the mechanical system for any binding, jamming, or blockage of the motor shaft or connected load, and eliminate the obstruction.
Review all relevant drive control loop parameters (e.g., gains, filters) to ensure they are correctly tuned for the application and motor.
Verify and correctly parameterize S-0-0159, Monitoring Window, to an appropriate value for the application's tolerance for deviation.
Reduce commanded acceleration or deceleration rates to remain within the drive's and mechanical system's capabilities.