F860

Overcurrent: Short in Powerstage

Indramat · ECODRIVE Controller

What does F860 mean?

This is a fatal error indicating an internal short circuit within the ECODRIVE DKC01.1/DKC11.1 drive's power stage, leading to excessive current flow. This fault immediately causes the drive to shut down to prevent further damage.

Common Causes

  • Internal failure of power semiconductor components (e.g., IGBTs) within the drive.
  • Motor winding short circuit or insulation breakdown causing high current demand.
  • Short circuit in motor cables or connection points (e.g., terminal box).
  • Severe mechanical overload or sudden jam causing excessive motor current.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect motor power cables from the ECODRIVE DKC01.1/DKC11.1 drive and check for short circuits between motor phases and to ground using a megohmmeter.

  2. 2

    Inspect the motor and load for any mechanical binding, obstructions, or excessive load that could cause extreme current.

  3. 3

    Verify motor winding integrity by measuring resistance between phases and insulation resistance to ground.

  4. 4

    If external checks are clear and the fault persists, it indicates an internal power stage failure; the ECODRIVE DKC01.1/DKC11.1 drive controller must be exchanged.

Browse all codes in this manual (24)