Indramat · Indradrive
A sudden surge of current exceeding the instantaneous rating was detected in the IndraDrive's power section, leading to an immediate shutdown to prevent damage. This is often caused by a short circuit in the motor or cabling, or a rapid acceleration of a high inertia load.
Click steps to track your progress.
Disconnect power and perform insulation resistance tests (megger) between motor phases and to ground on both the motor and motor cable.
Verify that the acceleration and deceleration ramps (e.g., S-0-0077 Ramp Time Pos, S-0-0078 Ramp Time Neg) are appropriately set for the application's inertia.
Check motor parameters in the drive (e.g., S-0-0010 Motor Nominal Current, S-0-0013 Motor Type) against the motor nameplate.
Inspect the motor and mechanical system for any binding or sudden impacts.
If the motor and cabling are verified good, the drive's power section may be faulty and require replacement.