Power Supply Phase Error
Indramat · dds 2.1 digital servo drive User Manual
What does S-0-0011 Bit 10 mean?
A Class 1 Diagnostic indicating an issue with one or more phases of the incoming three-phase AC power supply to the DDS 2.1 drive. This typically means a phase loss or significant imbalance, leading to a drive shutdown. The drive decelerates to zero speed and shuts down torque. This condition is reset only after the cause is cleared and the command 'Reset Class 1 Diagnostics' is received via the service channel.
Common Causes
- Loss of one or more phases of the incoming AC power supply.
- Blown fuse or tripped circuit breaker in one of the supply phases.
- Severe voltage imbalance between the incoming phases.
- Loose or corroded connection on one of the incoming power phases.
- Faulty phase detection circuit within the DDS 2.1 drive.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure the incoming three-phase AC supply voltages (L1-L2, L2-L3, L3-L1) at the DDS 2.1 input terminals to confirm all phases are present and balanced.
- 2
Check all fuses and circuit breakers in the input power line for continuity or tripped status.
- 3
Inspect all power wiring connections to the DDS 2.1 drive for tightness, corrosion, or damage on each phase.
- 4
Verify that the power supply network is stable and not experiencing phase loss upstream.
- 5
If the error persists and incoming power is stable, an internal fault in the drive's phase detection may be present.