Undervoltage in power section
Indramat · IndraDrive MPx02
What does E2026 mean?
The IndraDrive MPx02 has detected an undervoltage condition within its internal power section (DC bus voltage has dropped below a critical threshold). This is a warning state that precedes a fault if the condition persists, impacting drive performance and potentially leading to a controlled shutdown to protect the drive.
Common Causes
- Insufficient incoming AC mains voltage to the drive.
- Temporary voltage sag or brownout on the mains supply.
- Excessive current draw during heavy loading conditions leading to DC bus ripple or collapse.
- High resistance in the power cabling to the drive, causing voltage drop.
- Internal issues with the drive's DC bus capacitor bank or charging circuit.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure the incoming AC mains voltage at the drive input terminals (L1, L2, L3) and compare it to the drive's nominal voltage setting (P-0-0120).
- 2
Monitor the DC bus voltage (e.g., via drive diagnostics) to observe its behavior and confirm the undervoltage during operation, especially during acceleration or heavy load.
- 3
Inspect all power cable connections to the IndraDrive MPx02 for looseness, corrosion, or inadequate sizing that could cause voltage drops under load.
- 4
Reduce the mechanical load or adjust the application's duty cycle to minimize peak current demands if the undervoltage occurs during heavy transients.
- 5
If the supply voltage is stable and correct, but the warning persists, contact Indramat service for internal drive diagnostics.