11

Max Travel Lmt 1

Indramat · ServoDyn D Servo Drive

What does 11 mean?

This error occurs in Automatic Mode for Axis 1 if the commanded position is greater than the value configured in Parameter 12 (Maximum Travel Limit A1). The system detects an attempt to move Axis 1 beyond its defined maximum operational boundary.

Common Causes

  • The programmed command attempts to move Axis 1 above its Maximum Travel Limit set in Parameter 12.
  • Parameter 12 (Maximum Travel Limit A1) is set incorrectly or too low for the actual mechanical limits of Axis 1.
  • Overshoot of Axis 1 during acceleration or homing, causing it to briefly exceed the maximum limit.
  • If a Minimum Stroke is programmed, it may be exceeding the Maximum Travel limit.
  • Incorrect position gain (Parameter 05) or tuning, leading to poor positioning accuracy.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify that Parameter 12 (Maximum Travel Limit A1) is correctly set to reflect the actual maximum mechanical travel limit for Axis 1.

  2. 2

    If a Minimum Stroke is programmed in the CLM01.3-M, verify that it does not exceed the Maximum Travel limit.

  3. 3

    Adjust the user program to ensure that commanded positions for Axis 1 do not exceed the value specified in Parameter 12.

  4. 4

    Optimize the position gain (Parameter 05) for Axis 1 to improve acceleration and stopping accuracy if overshoot is observed.

  5. 5

    Inspect the mechanical system for any binding or obstructions that could restrict movement or cause overtravel.