Invalid Prg Cmd
Indramat · ServoDyn D Servo Drive
What does 15 mean?
This error occurs when the CLM01.3-M user program encounters an unrecognized or syntactically incorrect program command. The command is not part of the valid instruction set defined for the CLM01.3-M.
Common Causes
- A program command in the user program is misspelled, incomplete, or does not conform to the correct syntax.
- Attempt to use a program command that is not supported by the CLM01.3-M firmware or model.
- Corrupted user program data in the CLM01.3-M's memory.
- Parameter 84 (Start Task 2 & 3) is enabled with an invalid program command in Task 3.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Review the CLM01.3-M user program to identify the invalid program command and compare it against the list of valid commands in Chapter 5 (Programming).
- 2
Correct any misspelled or syntactically incorrect commands in the user program.
- 3
Ensure that all program commands used are appropriate for the CLM01.3-M model and its firmware version.
- 4
If Task 3 is in use, verify that all program commands within Task 3 are valid and that Parameter 84 is correctly configured.
- 5
Consider re-transmitting or re-entering the entire program to ensure data integrity and clear any potential memory corruption.