Marker Pulse 2?
Indramat · ServoDyn D Servo Drive
What does 32 mean?
This error occurs if the marker pulse from the Axis 2 encoder is detected too close (closer than 1/16 revolution) to the homing switch cam. This can lead to unreliable homing operations or incorrect home position detection for Axis 2.
Common Causes
- Homing switch cam for Axis 2 is physically positioned too close to the encoder's marker pulse detection point.
- Incorrect mechanical adjustment of the homing switch or the encoder itself for Axis 2.
- Faulty Axis 2 encoder producing an unstable or noisy marker pulse.
- Configuration parameters for homing (Parameter 48 or Parameter 50) are incorrect for Axis 2.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Adjust the physical position of the Axis 2 home limit switch cam by a distance equal to or greater than 1/3 of the Axis 2 Feed Constant.
- 2
Verify that Parameter 48 (Homing Setup A2) and Parameter 50 (Homing Setup I/O A2) for Axis 2 are correctly configured as per the manual (refer to Chapter 4).
- 3
Inspect the Axis 2 encoder for any physical damage or loose connections that could affect marker pulse generation.
- 4
Check the Axis 2 homing switch for proper mechanical actuation and reliable electrical signaling.
- 5
Use an oscilloscope to observe the Axis 2 encoder marker pulse signal and homing switch signal to identify timing or noise issues.