No Marker Pulse2
Indramat · ServoDyn D Servo Drive
What does 33 mean?
This error occurs if the marker pulse from the Axis 2 encoder is not detected within one full rotation during the Axis 2 homing cycle, or if a continuous marker pulse signal is present. This points to a problem with the marker pulse feedback for Axis 2.
Common Causes
- Disconnected or faulty wiring for the marker pulse at CLM01.3-M connector X2, pins 3 and 4.
- Defective Axis 2 encoder, failing to generate a marker pulse or generating a continuous pulse.
- Incorrectly set homing parameters (e.g., Parameter 48 or 49) preventing proper marker pulse search for Axis 2.
- Noise or interference on the encoder feedback lines disrupting Axis 2 marker pulse detection.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Switch the marker pulse wires at CLM01.3-M connector X2, pins 3 and 4 (if incorrect polarity is suspected).
- 2
Verify that the Axis 2 encoder is correctly installed and free from physical damage.
- 3
Inspect the Axis 2 encoder cable for any signs of damage, shorts, or poor shielding.
- 4
Review Parameter 48 (Homing Setup A2) and Parameter 49 (Homing Offset A2) for Axis 2 to ensure proper homing configuration.
- 5
If possible, use an oscilloscope to check for the presence and quality of the marker pulse signal directly at the encoder and at the CLM01.3-M input.