RS 01

RS Block # Wrong

Indramat · ServoDyn D Servo Drive

What does RS 01 mean?

This serial communication error occurs when the program command transmitted to the CLM01.3-M contains an invalid program block number. The block number sent via serial interface must be between 000 and 999.

Common Causes

  • The program block number in the serial command string is outside the valid range of 000-999.
  • Typographical error in the block number within the transmitted serial command.
  • Corrupted data transmission over the serial interface.
  • Sending device software bug generating incorrect block numbers.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify that the program block number being transmitted is between 000 and 999. Refer to Chapter 7 (Serial Interface) for the correct command format.

  2. 2

    Correct the program block number in the transmitted serial command to be within the valid range.

  3. 3

    Check the serial communication link (RS-232/422/485) for noise, interference, or incorrect cabling that could corrupt data.

  4. 4

    Re-transmit the program command after verifying the block number and overall command format.

  5. 5

    Ensure the sending device's software generates program block numbers correctly according to the CLM01.3-M specifications.