61

Overspeed

Kone · CMXC-022 Frequency Control Upgrade Kit

What does 61 mean?

An overspeed condition has been detected by the R&M Materials Handling Frequency Converter, or there is interference affecting the speed signal from the encoder connected to ENC1A. This can lead to uncontrolled motor speed, posing a safety risk if not corrected.

Common Causes

  • Motor overspeed detected
  • Interference in the speed signal connected to ENC1A

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the supply voltage

  2. 2

    Verify the load measurement operation and calibration

  3. 3

    Check the sensor cable grounding and inverter PE- connections

  4. 4

    Check or replace the speed sensor connected to ENC1A

Browse all codes in this manual (40)