84

Clutch supervision

Kone · CMXC-022 Frequency Control Upgrade Kit

What does 84 mean?

Clutch slipping has been detected in a chain hoist, or there's an issue with the speed feedback from ENC2A-B, by the R&M Materials Handling Frequency Converter. This indicates a loss of mechanical integrity or an encoder signal problem, potentially due to worn components or incorrect parameter settings (P8.7).

Common Causes

  • Clutch slipping detected (in chain hoists)
  • Worn chain or chain drive (in chain hoists)
  • Missing pulses in the signal connected to ENC2A-B
  • Parameter P8.7 (ENC2 Stall Pulse Limit) value is too high

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check and adjust the clutch mechanism

  2. 2

    Check and replace the chain and chain drive if worn

  3. 3

    Check or replace the speed sensor connected to ENC2A-B

  4. 4

    Lower the value of parameter P8.7 (ENC2 Stall Pulse Limit)

Browse all codes in this manual (40)