Kone · V3F25/18 drive
The V3F25/18 drive is prevented from operating until this fault is corrected. This indicates a general issue with the inverter's internal operation or its external control signals and feedback.
Click steps to track your progress.
Check connections of tachometer and thermal switch (XM2).
If Tacho fault counter (6_35) parameter is too sensitive, turn the elevator to RDF and back to Normal to reset it.
If LBR LED does not light, refer to AS-11.65.008 and circuit diagrams.
If LBR lights but LBE is not activated at start, check parameter (6_38).
If MLB is 'shutdown', check voltage in the supply and at terminals X10/16 in MLB (+24V).
Remove the U REF2 jumper.