LP1-Trip (Phase Failure)
Kuka · KR C2 Robot Controller
What does 32 mean?
This fault indicates a phase failure. For the KPS-600, it specifically refers to a mains phase failure, meaning an issue with the incoming AC power supply. For KSDs, it indicates a motor phase failure, meaning one or more phases supplying the motor are missing or unbalanced. Both conditions prevent proper operation and lead to drive shutdown.
Common Causes
- LP1-Trip: Phase failure detected on the main power supply (P1-17).
- Loss of one or more phases from the AC mains.
- Blown fuse in one of the supply phases.
- Internal wiring issue to the power input terminals.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure the voltage of each incoming AC mains phase (L1-L2, L2-L3, L3-L1) at the drive input terminals.
- 2
Verify voltage balance between phases — expect less than 2% deviation.
- 3
Measure the voltage of each motor output phase (U-V, V-W, U-W) during a run command.
- 4
Inspect all power connections from the mains supply to the drive and from the drive to the motor for tightness and corrosion.