PS1 Off
Power Supply 1 (Short Battery Backup) Not Present / Drive Bus Off
Kuka · Sunrise Cabinet Med Controller
What does PS1 Off mean?
The PS1 Voltage Green LED is OFF, indicating either that Power Supply 1 (with short battery backup) is not present or that the drive bus is in a 'BusPowerOff' state. This condition could prevent motor drives from receiving power, resulting in a loss of motion control.
Common Causes
- Power Supply 1 (PS1), potentially for short battery backup, is offline.
- Failure or disconnection of the PS1 unit.
- The drive bus voltage is too low or absent.
- Battery backup for PS1 has failed or is disconnected.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check the infeed at connector X1, verifying the presence and stability of the rated voltage of 27.1 V.
Verified technical data. Last updated: March 2026