Kuka · Sunrise Cabinet Med Controller
The STA2 Orange LED for the FPGA node is flashing at a rate other than 1 Hz (normal) or 10 Hz (boot phase), indicating an internal fault code within the FPGA node. This suggests a problem with the internal logic or operation of the FPGA, which can severely impact controller performance and stability.
Click steps to track your progress.
Check the infeed power supply at connector X1.
Verify the status of the PWR/3.3V LED (Item 6, Page 98). If it is lit, exchange the CCU_SR module.
If the PWR/3.3V LED is not lit, troubleshoot the 3.3V power supply (refer to 'PWR/3.3V Off (CIB_SR)' fault code for specific steps).
If power supply checks pass and the LED continues to flash, exchange the CCU_SR module.