EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Troubleshooting Course
  4. E.OHT
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

E.OHT

External Thermal Relay Operation

Mitsubishi Electric · FR-A800 Troubleshooting Course

What does E.OHT mean?

This fault occurs when the external thermal relay connected to the CS-SD terminals has tripped, indicating an overload condition detected by an external device. The FR-A800 inverter output is shut off to protect the motor and system. This fault is triggered when parameter T708 (Pr.186) (CS terminal function selection) is set to '7' (external thermal relay input) and the CS-SD terminal circuit becomes open.

Common Causes

  • Activation of an external thermal relay due to motor overload or excessive temperature.
  • Incorrect setting of parameter T708 (Pr.186) for external thermal relay input while the CS-SD terminals are open.
  • A break or open circuit in the wiring between the CS-SD terminals and the external thermal relay.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the motor and driven equipment for signs of overload, mechanical binding, or excessive temperature.

  2. 2

    Inspect the external thermal relay for proper operation, correct setpoint, and ensure its contacts are closed under normal conditions.

  3. 3

    Check the wiring between the FR-A800 inverter's CS-SD terminals and the external thermal relay for continuity and secure connections.

  4. 4

    Confirm parameter T708 (Pr.186) (CS terminal function selection) is set to '7' if an external relay is used, or reset to '6' (automatic restart after instantaneous power failure selection) if not used.

Browse all codes in this manual (16)
Verified technical data. Last updated: April 2026

Related Faults

E.CDOOutput Current Detection Value ExceededE.IPFInstantaneous Power FailureE.LFOutput Phase Loss
Source: Mitsubishi Electric FR-A800 Troubleshooting Course
Open Manual (Page 87)Search more codes in this manual