E.THM

Motor Overload Trip (Electronic Thermal O/L Relay)

Mitsubishi Electric · FR-A800 Troubleshooting Course

What does E.THM mean?

The FR-A800 inverter's internal electronic thermal overload relay has tripped, indicating that the motor has been subjected to a continuous overload condition exceeding its thermal capacity for an extended period. This protects the motor from overheating and damage.

Common Causes

  • Continuous mechanical overload on the motor, causing it to draw current above its rated value.
  • Incorrect electronic thermal overload relay setting in the FR-A800 inverter, not matching the motor's rated current.
  • Insufficient motor cooling or poor ventilation at the motor.
  • Motor winding damage or insulation degradation.
  • Parameter P001 (Pr.9) (Motor capacity) or P002 (Pr.10) (Motor rated current) are incorrectly set.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the motor and mechanical load for any binding, excessive friction, or blockages that could cause continuous overload.

  2. 2

    Verify the motor's rated current from its nameplate and ensure parameter P002 (Pr.10) (Motor rated current) is set correctly in the FR-A800 inverter.

  3. 3

    Check the motor's cooling fan and ensure adequate ventilation around the motor.

  4. 4

    Measure motor winding resistance and insulation resistance to ground to check for internal motor damage.

  5. 5

    If the motor operates at low speeds for extended periods, consider external cooling for the motor.

Browse all codes in this manual (16)
Verified technical data. Last updated: April 2026