OL

Stall Prevention (Overcurrent)

Mitsubishi Electric · FR-A800 Troubleshooting Course

What does OL mean?

This alarm indicates that the FR-A800 inverter's stall prevention function has activated due to an overcurrent condition, typically during acceleration, constant speed, or deceleration. The inverter attempts to prevent a trip by limiting the output current, which may result in reduced speed or torque. It is often a precursor to an OC trip if the condition persists.

Common Causes

  • Sudden load changes or mechanical issues causing the motor to draw excessive current.
  • Acceleration time (F010 (Pr.7)) or deceleration time (F011 (Pr.8)) set too short, causing rapid current changes.
  • Stall prevention level H500 (Pr.22) is set too low for the application's operating conditions.
  • Motor or drive capacity is undersized for the application.
  • Excessive supply voltage sag or fluctuation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the mechanical load for binding, excessive friction, or sudden load increases. Check for rail joint issues or reduction gear/wheel problems if applicable.

  2. 2

    Adjust acceleration time (F010 (Pr.7)) and deceleration time (F011 (Pr.8)) to longer values to reduce current peaks.

  3. 3

    Increase the stall prevention level H500 (Pr.22) (Stall prevention operation level) to allow higher current draw, but do not exceed motor or FR-A800 inverter ratings significantly.

  4. 4

    Verify the motor and inverter capacities are appropriate for the application.

  5. 5

    Monitor the power supply voltage for fluctuations or sags.

Browse all codes in this manual (16)
Verified technical data. Last updated: April 2026