ALM4

Output Short-Circuit Detection

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does ALM4 mean?

This signal is output when an output short-circuit is detected, specifically when an E.GF (Output side earth (ground) fault overcurrent) occurs while Pr.249 is set to '2'. This indicates a severe fault on the output side that has triggered a restricted reset condition for earth faults.

Common Causes

  • Output side earth (ground) fault overcurrent (E.GF) occurring when Pr.249 is set to '2'.
  • Short circuit or ground fault on the inverter output terminals, motor, or motor wiring.
  • Damage to the inverter's output power components causing a false short circuit detection.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Immediately turn OFF the control circuit power to reset the E.GF condition as required when Pr.249 = '2'.

  2. 2

    Inspect all motor power cables and connections for any visible damage, frayed insulation, or signs of a short circuit or ground fault.

  3. 3

    Measure the insulation resistance of the motor and power cables to ground using a megohmmeter. Expect values >1 MΩ.

  4. 4

    Check for continuity between motor phases and from each phase to ground. Verify no direct shorts exist.

  5. 5

    Review Pr.190 to Pr.196 settings to confirm which terminal outputs the ALM4 signal, ensuring it is correctly assigned and monitored.