Mitsubishi Electric · FR-E500 Inverter
This function stops the inverter output if a ground fault overcurrent (alarm output E.GF) is detected on the inverter's output (load) side, affecting the motor or its connection cable. This protection can be enabled or disabled at inverter startup using Pr. 249. If enabled (Pr. 249=1), there will be an approximate 20ms output delay at every start.
Click steps to track your progress.
Measure insulation resistance between motor phases (U, V, W) and ground using a megger to identify the exact location of the ground fault.
Inspect the motor connection cable for any signs of insulation damage, chafing, or improper routing.
Verify the setting of Pr. 249 (ground fault detection at start); set to '0' if startup detection is not required or causing nuisance trips.