Mitsubishi Electric · FR-E500 Inverter
The inverter output is shut off because the output current reached or exceeded approximately 200% of the rated current during the acceleration phase. This indicates that the motor load is too high for the acceleration rate, or there is an issue with the motor or wiring.
Click steps to track your progress.
Increase the acceleration time setting (e.g., Pr. 7 or Pr. 44) to allow for a gentler ramp-up.
Measure the motor load current during acceleration and compare it to the motor nameplate rated current.
Inspect motor cable and motor terminals for signs of short-circuit or ground fault.