Mitsubishi Electric · FR-E500 Inverter
This fault stops the inverter output if communication between the inverter and the Parameter Unit (PU) is suspended due to disconnection or errors. This occurs when specific settings (e.g., '2', '3', '16', or '17') are configured in Pr. 75, or if the number of successive communication errors exceeds the permissible retries when Pr. 121 is set to '9999' for RS-485 communication.
Click steps to track your progress.
Ensure the PU is securely fitted into its connector on the inverter.
Verify the setting of Pr. 75 (PU communication settings) and Pr. 121 (RS-485 communication retry count) to ensure they are appropriate for the desired communication method.
Inspect the PU cable and connectors for any signs of damage or wear.