Mitsubishi Electric · MELSEC iQ-R I/O Module
A load connected to a transistor output module fails to turn off, or may even turn on unexpectedly, when it operates with a minute current (0.1mA or lower). This behavior is attributed to the inherent leakage current present in the transistor output, which is sufficient to activate such low-current loads.
Click steps to track your progress.
Connect a resistor (several tens or hundreds of kΩ) in parallel across the load terminals. This provides a path for the transistor's leakage current, ensuring the load deactivates completely.