ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

F114

Send Failure (Recurring)

Mitsubishi Electric · MELSEC Q-series MELSECNET/H

What does F114 mean?

A send failure has occurred, and the error recurred even after a retry. This suggests a persistent issue with the physical network or addressing scheme, preventing successful data transmission.

Common Causes

  • Faulty network cables or incorrect wirings
  • Faulty network hardware
  • Electrical noise
  • Absence of terminating resistors (in bus networks)
  • Duplication of station numbers or control/remote master stations

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect network cables for damage, incorrect wiring, or loose connections

  2. 2

    Verify the presence and correct installation of terminating resistors, if applicable (bus networks)

  3. 3

    Check for sources of electrical noise

  4. 4

    Confirm all station numbers are unique and control/remote master station settings are not duplicated

  5. 5

    Check for faulty network hardware

Browse all codes in this manual (60)