Mitsubishi Electric · MELSEC System Q/L Series
This error indicates an incorrect layout or excessive configuration of special units (modules) on the base unit. It occurs when the number of connectable modules exceeds 10, when a module causes total I/O points to exceed 4096 (for L26CPU-BT) or 1024 (for L02CPU), or if a module is installed across an I/O point boundary. This fault results in the CPU stopping operation.
Click steps to track your progress.
Reduce the number of connectable modules to 10 or less.
Remove any module that causes the system's total I/O points to exceed 4096 (for L26CPU-BT) or 1024 (for L02CPU).
Replace the module installed at the end of the base unit with one whose occupied I/O points do not exceed the limit of 4096 or 1024 points.
Reset the CPU module and attempt to transition it to RUN mode.