EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. ALM4
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
ALM4

Output Short-Circuit Detection

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does ALM4 mean?

This signal is output when an output short-circuit is detected, specifically when an E.GF (Output side earth (ground) fault overcurrent) occurs while Pr.249 is set to '2'. This indicates a severe fault on the output side that has triggered a restricted reset condition for earth faults.

Common Causes

  • Output side earth (ground) fault overcurrent (E.GF) occurring when Pr.249 is set to '2'.
  • Short circuit or ground fault on the inverter output terminals, motor, or motor wiring.
  • Damage to the inverter's output power components causing a false short circuit detection.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Immediately turn OFF the control circuit power to reset the E.GF condition as required when Pr.249 = '2'.

  2. 2

    Inspect all motor power cables and connections for any visible damage, frayed insulation, or signs of a short circuit or ground fault.

  3. 3

    Measure the insulation resistance of the motor and power cables to ground using a megohmmeter. Expect values >1 MΩ.

  4. 4

    Check for continuity between motor phases and from each phase to ground. Verify no direct shorts exist.

  5. 5

    Review Pr.190 to Pr.196 settings to confirm which terminal outputs the ALM4 signal, ensuring it is correctly assigned and monitored.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

E. 1Option FaultE. 13Internal Circuit FaultE. 2Option Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 140)Search more codes in this manual