E14

Master/Slave System Configuration Error

Mitsubishi Electric · R410A Systems

What does E14 mean?

This error indicates incorrect DIP switch (SWS) settings on the indoor unit PCB for master/slave configuration, or an open circuit in the control wiring between master and slave units. This prevents proper communication and coordinated operation.

Common Causes

  • Incorrect designation of master and slave units in a multi-system.
  • Missing or incorrect master/slave configuration parameters.
  • Communication failure between units in a master/slave setup.
  • System requires a specific master unit which is absent or faulty.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the DIP switch (SWS) settings on the indoor unit PCB of both master and slave units are configured according to the system's master/slave documentation.

  2. 2

    Check continuity and secure connections of the control wiring between the master and slave indoor units using a multimeter.