Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
The inverter output is shut off due to a contact failure between the inverter and a plug-in option, or if a manufacturer setting switch on the plug-in option has been altered. Excessive electrical noise around the inverter can also contribute to this fault. This compromises the functionality of the plug-in option.
Click steps to track your progress.
Power down the inverter and physically re-seat the plug-in option board firmly into its slot.
Verify the position of all manufacturer setting switches (DIP switches) on the option board against the option board's instruction manual.
Inspect the option board connector pins and the inverter's option slot for any signs of damage, bending, or foreign material.
Check for proper grounding of the inverter chassis and all connected external equipment, ensuring ground resistance is below 1 Ohm.
Route control wiring (e.g., communication cables) separately from power wiring (e.g., motor cables) by at least 30 cm to reduce EMI.