This abnormality is detected if a message was transmitted, an acknowledgment (ACK) of receipt was received, but no response command returns. The transmitting side detects this abnormality every 10 seconds, 6 times continuously. The remote controller displays the address and attribute of the controller that did not reply (ACK).
Click steps to track your progress.
Check the transmission waveform and inspect for noise on the transmission wire.
Turn off the power supply of the outdoor unit, indoor unit, FRESH MASTER, or LOSSNAY simultaneously for 5 minutes or more, then turn the power on again. This may reset an accidental malfunction.
If the abnormality (A8) regenerates after a power cycle, the controller at the displayed address and attribute may be defective and require replacement.
Verify that the total transmission wire length does not exceed 1000m (656ft) and the remote controller line does not exceed 15m (49ft), as over-range extension can affect voltage and signal.
Confirm that the transmission wire type matches the specifications: With shield wire (CVVS, CPEVS) or With normal wire (no shield - VCTF, VCTFK, CVV, CVS, VVR, VVF, VCT) with a diameter of 1.25mm² [AWG16] or more.