Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
This error indicates a failure in serial communication. It can occur between the outdoor controller circuit board and the outdoor power circuit board, or between the outdoor controller circuit board and the M-NET board. Causes include broken wires, contact failures in connectors (CN, CNMNT, CND), defective communication circuits on the boards, or noise interference on the M-NET transmission wire.
Click steps to track your progress.
Check the connection of connectors CN and CN between the outdoor controller circuit board and the outdoor power circuit board for disconnections or contact failures.
Check the connection wire between the outdoor controller circuit board (CNMNT) and the M-NET board (CN and CND) for disconnection, looseness, or breaking.
Review the M-NET transmission wiring method for proper installation.
If communication between the outdoor controller and outdoor power board fails, replace the outdoor power circuit board.
If communication between the outdoor controller and outdoor power board fails, replace the outdoor controller circuit board.